🔋

Voltage Drop Calculator

Calculate voltage drop across any cable run. Enter wire gauge or cross-section, current load and one-way distance to get voltage drop in volts, percentage drop and NEC/IEC compliance status.

NEC & IEC Standards AWG & mm²
System Type
Voltage Drop
0%3% limit10%+
Resistance per metre (2-way or √3)
Total cable resistance
Voltage drop
Percentage voltage drop
Remaining voltage at load
NEC/IEC compliance status
💡 Wire Upgrade Recommendation
Formulas Used
Conductor resistance:
R_conductor = ρ × L / A    [Ω]
  ρ_Cu = 1.724 × 10²» Ω·m  |  ρ_Al = 2.82 × 10²» Ω·m

Single-phase (2-wire):
V_drop = 2 × I × R_conductor

Three-phase (3-wire, balanced):
V_drop = √3 × I × R_conductor

Percentage:
% drop = (V_drop / V_supply) × 100

What is Voltage Drop and Why Does It Matter?

Voltage drop is the reduction in voltage along a cable caused by the cable's electrical resistance. Every conductor has resistance — even copper — and when current flows through that resistance, energy is lost as heat and the voltage at the far end of the cable is lower than at the source. The formula is simply:

V_drop = I × R_total

Excessive voltage drop causes equipment to run below its rated voltage, which can lead to: motor overheating, reduced lighting output, nuisance tripping of electronic devices, and wasted energy. Even a seemingly small 5% drop on a 230 V supply means the load only receives 218.5 V.

NEC and IEC Voltage Drop Limits

Regulatory standards define maximum permissible voltage drops to protect equipment and ensure safe operation:

  • NEC (NFPA 70): Recommends ≤3% drop on branch circuits and ≤5% total (feeder + branch). These are recommendations in the NEC, not mandatory requirements — though local codes may make them mandatory.
  • IEC 60364-5-52: Recommends ≤3% for lighting circuits and ≤5% for other uses (motors, heating, etc.).
  • AS/NZS 3000 (Wiring Rules): Maximum 5% from supply point to any point of use.
  • BS 7671 (UK): 3% for lighting, 5% for other circuits under normal conditions.

The default limit in this calculator is 3% — the stricter NEC/IEC standard for branch circuits and lighting.

Wire Resistance Reference Table

Resistance values shown are DC resistance at 20°C. AC resistance is slightly higher due to skin effect, especially at larger gauges.

AWG mm² (approx.) Cu Resistance (mΩ/m) Al Resistance (mΩ/m)
142.088.2913.55
123.315.218.52
105.263.285.36
88.372.063.37
613.31.302.12
421.20.8141.33
233.60.5130.839
142.40.4070.665
0 (1/0)53.50.3220.527
00 (2/0)67.40.2560.418
000 (3/0)85.00.2030.332
0000 (4/0)107.20.1610.263
1.511.4918.79
2.56.9011.28
44.317.05
62.874.70
101.722.82
161.081.76
250.6901.13
350.4930.806
500.3450.564

Frequently Asked Questions

The NEC recommends a maximum voltage drop of 3% for branch circuits and 5% for the total system (feeder + branch). IEC 60364 recommends 3% for lighting and 5% for other circuits. Exceeding these limits can cause equipment to malfunction, motors to overheat, and electronics to behave erratically. Some sensitive loads (medical equipment, precision instruments) require even tighter limits of 1–2%.
Voltage drop is proportional to wire length because resistance increases linearly with length (R = ρ × L / A). Double the wire length, double the resistance, double the voltage drop. This is why long cable runs — to outbuildings, garden sockets, pool pumps, or large factory floors — often need significantly larger wire gauges than the current rating alone would suggest. Always calculate voltage drop for any run longer than 15–20 metres.
For single-phase 2-wire circuits, current must travel to the load and return on two conductors, so the effective conductor length is doubled: V_drop = 2 × I × R_conductor. For balanced three-phase 3-wire circuits, the three phases share the return path and the factor becomes √3 (≈1.732): V_drop = √3 × I × R_conductor. Three-phase is more efficient — for the same voltage drop you can use smaller wire or run longer distances.
The most practical solutions are: (1) Increase wire size — go up one or two AWG sizes or choose a higher mm² cross-section; (2) Shorten the run — move the distribution board or sub-panel closer to the load; (3) Use three-phase where possible for long high-current runs; (4) Reduce current by splitting the load across multiple circuits; (5) Boost the supply voltage slightly at the source where local regulations and equipment ratings allow.