Power Factor Calculator

Calculate real power, reactive power, apparent power and power factor from any two known values. Includes power triangle visualisation and capacitor bank sizing for power factor correction to target PF.

PF Correction Capacitor Sizing Power Triangle
Known Values
Results
Power Factor
0 (worst)0.850.951.0 (unity)
Real Power P
Reactive Power Q
Apparent Power S
Power Factor PF
Phase Angle θ
PF Correction Inputs
Correction Results
Current Reactive Power Q₁
Target Reactive Power Q₂
Current Apparent Power S₁
Target Apparent Power S₂
Required Qc: —
Capacitance: —
Connection type
Voltage used for C calc
Three-phase result is per capacitor (delta connection, line-to-line voltage). For star connection, multiply C by 3. Always verify with a licensed electrician before installation.

What is Power Factor?

Power factor (PF) is the ratio of real power (kW) to apparent power (kVA) in an AC electrical system. It is a dimensionless number between 0 and 1 (or expressed as a percentage) that describes how effectively electrical power is being converted into useful work. A PF of 1.0 means all the supplied current performs real work; lower values indicate that some current flows back and forth as reactive power without doing useful work.

Mathematically: PF = P (kW) / S (kVA) = cos θ, where θ is the phase angle between voltage and current waveforms.

Why Does Power Factor Matter?

Low power factor increases the apparent current drawn from the supply for the same amount of real work. This has several consequences:

How to Improve Power Factor

The most common and cost-effective method is adding capacitor banks at the main distribution board or at individual motor terminals. Capacitors supply reactive power locally, reducing the reactive component drawn from the grid.

Frequently Asked Questions

A power factor of 0.95 or above is generally considered excellent. Most utilities target 0.90–0.95 as a minimum for commercial and industrial customers. Unity PF (1.0) means no reactive power is drawn. Below 0.85, most utilities impose surcharges.
Power factor can be measured with a dedicated power factor meter, a clamp-type power analyser, or most modern smart meters and energy management systems. It can also be calculated indirectly: read real power in kW and apparent power in kVA from your meter display, then PF = kW ÷ kVA.
Low PF forces the utility to supply higher currents through its cables, transformers and switchgear for the same useful power delivered. This increases resistive losses throughout the network and requires larger infrastructure. Penalties recover these extra costs and incentivise customers to install correction equipment.
Use the "Correct PF" tab above. Enter your current measured PF, the target PF (typically 0.95), your load's real power in kW, system frequency and voltage. The calculator outputs the required reactive compensation in kVAR and the exact capacitance in µF. Always have the installation reviewed and commissioned by a qualified electrician.