⚙️

Motor Current Calculator

Calculate full-load amps, starting current, overload relay setting and recommended MCB or fuse size for any single-phase or three-phase AC motor. Supports kW and HP input with efficiency and power factor.

Single & Three-PhaseStarter & Protection Sizing
Single-Phase Motor Inputs
= 5.000 kW
Full-Load Current (FLA)
Amperes at full mechanical load
Starting Current
A (DOL)
Overload Relay
A (set at 115% FLA)
Recommended MCB
A (next std size)
Input Power (kW)
Apparent Power (kVA)
MCB / MCCB Size— A
Contactor Rating— A
Recommended Cable Size
Overload Relay Range
Note: These values are calculated estimates. Always verify with motor nameplate data and applicable local electrical codes. Starting current multipliers are typical values; actual inrush may vary by motor design and load.

How to Calculate Motor Full-Load Amps

The full-load ampere (FLA) rating of an AC motor depends on its power, supply voltage, power factor, and efficiency. The formulas are:

Single-phase motor:

FLA = (kW × 1000) / (V × PF × η/100)

Three-phase motor:

FLA = (kW × 1000) / (√3 × V × PF × η/100)

Once FLA is known, protection and control equipment is sized as follows:

Recommended MCB Sizes for Common Motors

Motor (kW)≈HP3-Phase FLA (415V)MCB SizeContactor
0.37 kW0.5 HP~0.9 A2 A9 A
0.75 kW1 HP~1.7 A4 A9 A
1.5 kW2 HP~3.4 A6 A9 A
2.2 kW3 HP~5.0 A10 A12 A
3.7 kW5 HP~8.4 A16 A16 A
5.5 kW7.5 HP~12.5 A20 A16 A
7.5 kW10 HP~17 A25 A25 A
11 kW15 HP~25 A40 A32 A
15 kW20 HP~34 A50 A40 A
22 kW30 HP~50 A80 A65 A
37 kW50 HP~84 A125 A95 A

Values at PF = 0.85, η = 90%, 415V three-phase. Actual nameplate values take precedence.

Motor Starting Methods Compared

MethodStarting CurrentStarting TorqueCostBest For
Direct On-Line (DOL)6–8× FLA100% (full)LowestSmall motors <5 kW, fans, pumps
Star-Delta~2× FLA (line)33% of DOLMediumMedium motors 5–75 kW, lightly loaded starts
Soft Starter1.5–3× FLAAdjustableMedium-HighConveyors, pumps, compressors
VFD (Variable Frequency Drive)1.0–1.5× FLAFull torque at 0 RPMHighestVariable-speed loads, energy saving, precise control

Star-Delta starters reduce voltage to 57.7% during the star phase, reducing starting current to approximately 1/3 of DOL — but also reducing torque to 1/3. They are only suitable when the load can start unloaded or with low inertia.

Frequently Asked Questions

Full-load current (FLA) is the rated current a motor draws when operating at its nameplate horsepower or kilowatt rating under full mechanical load. For a single-phase motor: FLA = (kW × 1000) / (V × PF × η). For a three-phase motor: FLA = (kW × 1000) / (√3 × V × PF × η). FLA is the reference value for sizing overload relays, cables, MCBs, and contactors.
A 5HP (3.73 kW) three-phase motor at 415V with PF 0.85 and 90% efficiency draws approximately 6.8A FLA. The MCB should be sized at 125% of FLA = 8.5A, so the next standard size of 10A MCB is recommended. For DOL starting (7× FLA ≈ 47A inrush), use a Type C or D characteristic MCB to avoid nuisance tripping on the startup surge.
At startup the motor rotor is stationary and back-EMF is zero, so the motor behaves like a short-circuited transformer. Current is limited only by low winding resistance and leakage reactance, causing 6–8× full-load current during DOL starting. As the rotor accelerates, back-EMF builds up and current falls to FLA within 2–5 seconds. High starting current can cause voltage dips that affect other equipment on the same supply.
Service factor (SF) is a multiplier on the nameplate power rating indicating how much overload the motor can sustain continuously without damage. A 1.15 SF motor rated 10 kW can handle 11.5 kW continuously. When sizing protection equipment, multiply FLA by the service factor to avoid nuisance tripping on allowed overloads. Standard motors have SF = 1.0; premium motors often carry SF = 1.15.